Central loose tube, single sheathed cable, iRP-increased rodent protected outdoor- use, UV.LDPE sheath - black, Fca, 01 x 12 fibers G657A1

Štampa PDF

 

 

linija

 

Proizvođač:  Reichle & De-Massari 

CLT A-DQ(ZN)B2Y 

Kataloška oznaka: R851102

 

slika

Cena: zvati 

Jed.mere: m       PDV: 20 % 

Garancija: 5 godina 

 

 

Technical Data

Cable family code OT1GL
Cable type Central loose tube cable
Cable application outdoor use
DoP number D9907
Fiber color coding 1.-12.: red, green, blue, yellow, white, grey, brown, violet, turquoise, black, orange, pink
Fiber count per tube 12
Loose tube count 1
Loose tube diameter 2.8 mm
Armor Intensified rodent protection
Outer sheath thickness 1.1 mm
Outer sheath material UV stable LDPE
Outer sheath color black
Sheath marking Ink-Jet, white
Cable outer diameter 6.5 mm
Cable weight 37.0 kg/km / 25 lbs/1000ft
DIN / VDE 0888 code A-DQ(ZN)B2Y
CPR test method EN 50575, EN 13501-6
Standard put-up length on drum 2100 m ± 5%
CPR classification Fca

Mechanical Data

In-service tensile strength 600 N
In-service tensile strength acceptance criteria Δα ≤ 0,05 dB
In-service tensile strength test method EN 60794-1-21:E1
Installation tensile strength 1800 N
Installation tensile strength acceptance criteria Δα ≤ 0,05 dB after test
Installation tensile strength test method IEC 60794-1-21:E1
Crush resistance long term 1000 N/100mm
Long-term crush resistance acceptance criteria Δα ≤ 0,05 dB prior release, no damage
Long-term crush resistance test method IEC 60794-1-21:E3A
Short-term crush resistance 2000 N/100mm
Short-term crush resistance acceptance criteria Δα ≤ 0,05 dB after release, no damage
Short-term crush resistance test method IEC 60794-1-21:E3A
Impact resistance 10 Nm, 3 impacts, d=20 mm, R=300 mm
Impact resistance acceptance criteria Δα ≤ 0,05 dB after test, no damage
Impact resistance test method IEC 60794-1-21:E4
Torsion L = 1 m, rotation angle ±180°, 10 cycles
Torsion acceptance criteria no damage
Torsion test method IEC 60794-1-21:E7
Repeated bending R=20 x cable diameter, 25 cycles
Repeated bending acceptance criteria no damage
Repeated bending test method IEC 60794-1-21:E6
Cable bend d=20 x cable diameter, 4 turns, 3 cycles
Cable bend acceptance criteria Δα ≤ 0,05 dB after test, no damage
Cable bend test method IEC 60794-1-21:E11A
Minimum bend radius in service 100 mm
Minimum bend radius during installation 130 mm

Environmental Characteristics

Temperature cycling -20 °C +70 °C / -4 °F +158 °F
Temperature cycling acceptance criteria Δα ≤ 0,05 dB
Temperature cycling test method IEC 60794-1-22:F1
Reversible temperature cycling -25 °C +70 °C / -13 °F +158 °F
Reversible temperature cycling acceptance criteria Δα ≤ 0,15 dB, reversible
Reversible temperature cycling test method IEC 60794-1-22:F1
Operation temperature -20 °C to +70 °C / -4 °F to +158 °F
Storage / Transport temperature -25 °C to +70 °C / -13 °F to +158 °F
Thermal load 1.01 MJ/m
Flammability vertical cable bundle Pass
Flammability vertical cable bundle test method EN 60332-3-22 (cat. A)
Smoke density Pass
Smoke density test method EN 61034-1, EN 61034-2
Halogen free, acid gases Pass
Halogen free, acid gases test method EN 60754-2
2015 / 863 / EU - RoHS 3 Pass

 

 

 

 

 