Central loose tube, single sheathed cable, RP-rodent protected, outdoor- use, UV.LDPE sheath - black, Fca, 01 x 24 fibers G657A1

Štampa PDF

 

 

linija

 

Proizvođač:  Reichle & De-Massari 

CLT A-DQ(ZN)B2Y 

Kataloška oznaka: R855518

 

slika

Cena: zvati 

Jed.mere: m       PDV: 20 % 

Garancija: 5 godina 

 

 

 

Cable family code OX1EL
Cable type Central loose tube cable
Cable version n.a.
Cable application outdoor use
DoP number D9906
Fiber type G.657.A1
Fiber count 24
Fiber color coding 1.-12.: red, green, blue, yellow, white, gray, brown, violet, turquoise, black, orange, pink13.-24.: red, green, blue, yellow, white, gray, brown, violet, turquoise, natural, orange, pink(ring-marked)
Fiber count per tube 24
Loose tube count 1
Loose tube diameter 3.5 mm
Armor Rodent protection
Outer sheath thickness 1.1 mm
Outer sheath material UV stable LDPE
Outer sheath color black
Sheath marking Ink-Jet, white
Cable outer diameter 6.5 mm
Cable weight 37.0 kg/km / 25 lbs/1000ft
DIN / VDE 0888 code A-DQ(ZN)2Y
CPR test method EN 50575, EN 13501-6
Standard put-up length on drum 2100 m ± 5%
CPR classification Fca
Mechanical Data
In-service tensile strength 300 N
In-service tensile strength acceptance criteria Δα ≤ 0,05 dB after test
In-service tensile strength test method IEC 60794-1-21:E1
Installation tensile strength 1000 N
Installation tensile strength acceptance criteria Δα ≤ 0,05 dB
Installation tensile strength test method IEC 60794-1-21:E1
Crush resistance long term 1000 N/100mm
Long-term crush resistance acceptance criteria Δα ≤ 0,05 dB prior release, no damage
Long-term crush resistance test method IEC 60794-1-21:E3A
Short-term crush resistance 2000 N/100mm
Short-term crush resistance acceptance criteria Δα ≤ 0,05 dB after release, no damage
Short-term crush resistance test method IEC 60794-1-21:E3A
Impact resistance 10 Nm, 3 impacts, d=20 mm, R=300 mm
Impact resistance acceptance criteria Δα ≤ 0,05 dB after test, no damage
Impact resistance test method IEC 60794-1-21:E6
Torsion L = 1 m, rotation angle ±180°, 10 cycles
Torsion acceptance criteria no damage
Torsion test method IEC 60794-1-21:E7
Repeated bending R=20 x cable diameter, 25 cycles
Repeated bending acceptance criteria Δα ≤ 0,05 dB after test, no damage
Repeated bending test method IEC 60794-1-21:E6
Cable bend d=20 x cable diameter, 4 turns, 3 cycles
Cable bend acceptance criteria Δα ≤ 0,05 dB after test, no damage
Cable bend test method IEC 60794-1-21:E11A
Minimum bend radius in service 100 mm
Minimum bend radius during installation 130 mm
Environmental Characteristics
Temperature cycling -20 °C +70 °C / -4 °F +158 °F
Temperature cycling acceptance criteria Δα ≤ 0,15 dB, reversible
Temperature cycling test method IEC 60794-1-22:F1
Reversible temperature cycling -25 °C +70 °C / -13 °F +158 °F
Reversible temperature cycling acceptance criteria Δα ≤ 0,15 dB, reversible
Reversible temperature cycling test method IEC 60794-1-22:F1
Operation temperature -20 °C to +70 °C / -4 °F to +158 °F
Storage / Transport temperature -25 °C to +70 °C / -13 °F to +158 °F
Thermal load 1.13 MJ/m
2015 / 863 / EU - RoHS 3 Pass


 

 

 

 

 

 

 

linija

Početak strane